What is a BTU?
A British Thermal Unit (BTU) is a unit of heat energy: roughly the energy needed to raise the temperature of one pound of water by 1°F. Heating and cooling equipment is rated in BTU per hour (BTU/h), the rate at which it adds or removes heat. One watt is about 3.412 BTU/h, and one "ton" of air conditioning is 12,000 BTU/h, the cooling rate of melting a ton of ice over a day.
AC BTU calculator
The air conditioner mode starts from a base of about 20 BTU/h per square foot plus 2,500 BTU/h for a room with a ceiling of 8 ft or less, then adjusts for the room itself.
- Ceiling height: each foot above 8 ft adds about 1,000 BTU/h up to 10 ft, with smaller additions above that. Large spaces over 500 ft² scale the addition up.
- Insulation: good insulation removes 20 percent and poor insulation adds 20 percent.
- Sun exposure: reduce by 10 percent for a heavily shaded room and add 10 percent for a very sunny one.
- Climate: a cold climate removes 15 percent and a hot climate adds 20 percent.
- Floor: an entire second floor or above needs 10 percent more, since heat rises.
- Occupants: add 600 BTU/h for each person beyond two who regularly uses the room.
- Room type: add 1,000 BTU/h for a living room and 4,000 BTU/h for a kitchen.
Worked example
A 400 ft² living room with an 8 ft ceiling starts at 20 × 400 + 2,500 = 10,500 BTU/h. If it is very sunny, add 10 percent to reach 11,550 BTU/h. Add 1,000 for a living room and 2 × 600 = 1,200 for four regular occupants, for a total of 13,750 BTU/h, a little over one ton.
For reference, ENERGY STAR's room air conditioner chart gives these capacities for an average room:
| Area (ft²) | Capacity (BTU/h) |
|---|---|
| 100 to 150 | 5,000 |
| 150 to 250 | 6,000 |
| 250 to 300 | 7,000 |
| 300 to 350 | 8,000 |
| 350 to 400 | 9,000 |
| 400 to 450 | 10,000 |
| 450 to 550 | 12,000 |
| 550 to 700 | 14,000 |
| 700 to 1,000 | 18,000 |
| 1,000 to 1,200 | 21,000 |
| 1,200 to 1,400 | 23,000 |
| 1,400 to 1,500 | 24,000 |
| 1,500 to 2,000 | 30,000 |
| 2,000 to 2,500 | 34,000 |
General purpose heating or cooling calculator
For heating, or for spaces that do not fit the AC rules, size the equipment from the surfaces that lose or gain heat and the temperature change you need. Floor and ceiling count at 0.2 BTU/h per square foot per °F each, and walls at 0.4.
The insulation multiplier is 0.6 for a well-insulated space, 1 for normal construction and 2.1 for a drafty space with many windows.
Worked example
A 20 by 25 ft room with an 8 ft ceiling has 500 ft² of floor and 720 ft² of walls. To keep it at 75°F when it is 30°F outside, the temperature increase is 45°F. With normal insulation, the heater should supply about 45 × (0.4 × 500 + 0.8 × 45 × 8) = 45 × 488 = 21,960 BTU/h, or about 6.4 kW.
Size and ceiling height
Smaller spaces need fewer BTUs. Typical sizing guidance assumes 8 ft ceilings. Rooms with vaulted or high ceilings contain more air and need more capacity.
Insulation condition
Windows and gaps around doors lose far more heat than well-insulated walls. Older homes with dated insulation usually rate as poor, newer homes with modern insulation and double-glazed windows as good. Upgrading insulation and sealing leaks is often cheaper than buying a larger unit.
Desired temperature increase or decrease
Most people are comfortable between 70 and 80°F. The temperature change is the difference between the outdoor temperature and your target. For a Boston winter night at about −5°F with a 75°F target, that is an 80°F increase. For an Atlanta winter at 30°F, it is 45°F. Extreme climates need much more capacity than mild ones.
Other factors
- Do not oversize. An oversized air conditioner cools the room before it removes humidity, leaving it clammy, and short cycling wears the unit out sooner. An undersized unit runs constantly.
- Condenser placement. Put the outdoor unit on the shadiest side of the house, often north or east, but keep plants from blocking airflow.
- Ceiling fans improve circulation and reduce hot spots, so thermostats read more accurately.
- Roof color. Dark roofs absorb more solar heat than light ones.
- Age and refrigerant. Units lose efficiency over time, and a low refrigerant charge can cut efficiency by half or more.
- House shape. A long, narrow house has more exterior wall than a square one of the same area, so it gains and loses heat faster.
For whole-house systems, a professional Manual J load calculation accounts for orientation, window area, ductwork and local design temperatures in detail. See ENERGY STAR for room unit guidance.