What is voltage drop?
Every conductor resists the flow of current a little. When current passes through a wire, part of the supply voltage is spent pushing it through that resistance, so the voltage that reaches the load is lower than the voltage at the panel. That loss is the voltage drop. In a DC circuit the opposition is simple resistance. In an AC circuit it is impedance, which combines resistance with the reactance caused by the alternating magnetic field around the conductor.
Too much drop shows up as dim or flickering lights, heaters that never reach temperature and motors that run hot, draw extra current and wear out early. A widely used design target is to keep the drop under 3% on a branch circuit and under 5% for the feeder and branch combined at full load.
What affects voltage drop
- Conductor material. Copper conducts better than aluminum, so a copper wire of the same size drops less voltage. Silver is slightly better than copper and gold slightly worse.
- Wire size. A larger cross-section means lower resistance and less drop. In the AWG system a smaller gauge number is a thicker wire.
- Length. Resistance grows in direct proportion to length, so doubling the run doubles the drop.
- Current. Drop is proportional to the current flowing, so heavier loads lose more voltage.
Voltage drop formulas
Three phase: VD = 1.732 × Z × L × I ÷ n
Here Z is the conductor impedance per unit length, L is the one-way length of the run, I is the load current and n is the number of parallel conductor sets. The factor of 2 accounts for current going out on one conductor and back on the other. In a balanced three-phase circuit the return currents partly cancel, so the factor becomes the square root of 3, about 1.732.
For AC circuits the NEC tab uses the effective impedance from NEC Chapter 9, Table 9:
R is the AC resistance and XL the inductive reactance for the chosen size, metal and conduit (steel conduit raises the reactance and, for larger sizes, the resistance). At a power factor of 1 the impedance is simply the resistance.
Worked example
A single-phase 120 V circuit uses 3 AWG copper in steel conduit with a power factor of 0.85. The run is 500 feet (0.1524 km) and the load draws 1 amp. Table 9 lists R = 0.82 Ω/km and XL = 0.194 Ω/km, so Z = 0.82 × 0.85 + 0.194 × 0.5268 = 0.7992 Ω/km. The drop is 2 × 0.7992 × 0.1524 × 1 = 0.24 V, or 0.20% of 120 V, leaving 119.76 V at the load. Increase the current to 10 amps and the drop rises tenfold to 2.44 V (2.03%).
Finding the minimum wire size
The minimum wire size tab runs the same calculation for every NEC conductor size, from 14 AWG up to 1000 kcmil, and picks the smallest one whose drop stays within the limit you set. The full table is shown so you can see how much headroom the next size up would buy. Remember that the conductor must also be large enough for the current it carries (its ampacity), which is a separate code requirement from voltage drop.
Typical AWG wire sizes
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Copper resistance (Ω/1000ft, DC 20 °C) |
|---|---|---|---|---|
| 4/0 | 0.4600 | 11.684 | 107 | 0.0490 |
| 1/0 | 0.3249 | 8.252 | 53.5 | 0.0983 |
| 2 | 0.2576 | 6.544 | 33.6 | 0.1563 |
| 4 | 0.2043 | 5.189 | 21.2 | 0.2485 |
| 6 | 0.1620 | 4.115 | 13.3 | 0.3951 |
| 8 | 0.1285 | 3.264 | 8.37 | 0.6282 |
| 10 | 0.1019 | 2.588 | 5.26 | 0.9989 |
| 12 | 0.0808 | 2.053 | 3.31 | 1.588 |
| 14 | 0.0641 | 1.628 | 2.08 | 2.525 |
Ways to reduce voltage drop
Move up one or two wire sizes, shorten the run by relocating the panel or load, run conductors in parallel, raise the system voltage (the same power at 240 V needs half the current of 120 V), or switch from aluminum to copper. On long three-phase feeders, improving the power factor also lowers the effective impedance.