Voltage Drop Calculator

About this calculator

The Voltage Drop Calculator estimates how many volts are lost along a run of wire. Pick the wire size and material, conduit type, power factor, system voltage, phase, number of parallel sets, one-way distance and load current, and you get the voltage drop, the drop as a percent of the supply, and the voltage left at the load.

Use the NEC tab for code-based AC impedance values, the estimated tab for a resistivity-based figure (including silver and gold), the custom tab when you have a manufacturer's impedance, or the minimum wire size tab to find the smallest conductor that keeps the drop under your limit.

Wire material
Material of conduit
Between 0 and 1. Used for AC circuits only.
volts
amps
%
Embed this calculator

Paste this code into a Custom HTML block on your site. The calculator fits the width of the block. Adjust the height in the code if you want more room for results.

Find this widget in the publisher directory

What is voltage drop?

Every conductor resists the flow of current a little. When current passes through a wire, part of the supply voltage is spent pushing it through that resistance, so the voltage that reaches the load is lower than the voltage at the panel. That loss is the voltage drop. In a DC circuit the opposition is simple resistance. In an AC circuit it is impedance, which combines resistance with the reactance caused by the alternating magnetic field around the conductor.

Too much drop shows up as dim or flickering lights, heaters that never reach temperature and motors that run hot, draw extra current and wear out early. A widely used design target is to keep the drop under 3% on a branch circuit and under 5% for the feeder and branch combined at full load.

What affects voltage drop

  • Conductor material. Copper conducts better than aluminum, so a copper wire of the same size drops less voltage. Silver is slightly better than copper and gold slightly worse.
  • Wire size. A larger cross-section means lower resistance and less drop. In the AWG system a smaller gauge number is a thicker wire.
  • Length. Resistance grows in direct proportion to length, so doubling the run doubles the drop.
  • Current. Drop is proportional to the current flowing, so heavier loads lose more voltage.

Voltage drop formulas

DC or single phase: VD = 2 × Z × L × I ÷ n
Three phase: VD = 1.732 × Z × L × I ÷ n

Here Z is the conductor impedance per unit length, L is the one-way length of the run, I is the load current and n is the number of parallel conductor sets. The factor of 2 accounts for current going out on one conductor and back on the other. In a balanced three-phase circuit the return currents partly cancel, so the factor becomes the square root of 3, about 1.732.

For AC circuits the NEC tab uses the effective impedance from NEC Chapter 9, Table 9:

Z = R × PF + XL × sin(arccos PF)

R is the AC resistance and XL the inductive reactance for the chosen size, metal and conduit (steel conduit raises the reactance and, for larger sizes, the resistance). At a power factor of 1 the impedance is simply the resistance.

Worked example

A single-phase 120 V circuit uses 3 AWG copper in steel conduit with a power factor of 0.85. The run is 500 feet (0.1524 km) and the load draws 1 amp. Table 9 lists R = 0.82 Ω/km and XL = 0.194 Ω/km, so Z = 0.82 × 0.85 + 0.194 × 0.5268 = 0.7992 Ω/km. The drop is 2 × 0.7992 × 0.1524 × 1 = 0.24 V, or 0.20% of 120 V, leaving 119.76 V at the load. Increase the current to 10 amps and the drop rises tenfold to 2.44 V (2.03%).

Finding the minimum wire size

The minimum wire size tab runs the same calculation for every NEC conductor size, from 14 AWG up to 1000 kcmil, and picks the smallest one whose drop stays within the limit you set. The full table is shown so you can see how much headroom the next size up would buy. Remember that the conductor must also be large enough for the current it carries (its ampacity), which is a separate code requirement from voltage drop.

Typical AWG wire sizes

AWGDiameter (in)Diameter (mm)Area (mm²)Copper resistance (Ω/1000ft, DC 20 °C)
4/00.460011.6841070.0490
1/00.32498.25253.50.0983
20.25766.54433.60.1563
40.20435.18921.20.2485
60.16204.11513.30.3951
80.12853.2648.370.6282
100.10192.5885.260.9989
120.08082.0533.311.588
140.06411.6282.082.525

Ways to reduce voltage drop

Move up one or two wire sizes, shorten the run by relocating the panel or load, run conductors in parallel, raise the system voltage (the same power at 240 V needs half the current of 120 V), or switch from aluminum to copper. On long three-phase feeders, improving the power factor also lowers the effective impedance.

Frequently asked questions

What is an acceptable voltage drop?
A common design guideline is no more than 3% on a branch circuit and no more than 5% for the feeder and branch circuit combined at full load.
Why is distance entered one way?
The formula already doubles the length for the out-and-back path in DC and single-phase circuits, so you enter only the distance from the source to the load.
Does conduit type change the voltage drop?
Yes, slightly. Steel conduit increases the inductive reactance of AC conductors and, for larger sizes, their effective resistance, so the drop is a little higher than in PVC or aluminum conduit.
How do parallel conductors help?
Running two or more sets of conductors per phase divides the current between them, which divides the voltage drop by the number of sets.

Formulas and sample results on this page were checked against independent references. Page last reviewed or updated . How we verify calculators. Project led by Shaun Connell.